SPECIFICATION
| Input Power | 90 to 264 Volts AC, 1ø, 50/60 Hz, 1800 VA. |
| AC Voltage Amplitude | |
| Accuracy: | ±0.05 % reading + 0.02 % range typical, ±0.15 % reading + 0.05 % range maximum |
| Resolution: | .01 |
| Measurements: | AC RMS |
| Ranges: | 30, 150, 300V |
| AC Current Amplitude | |
| Accuracy: | ±0.05 % reading + 0.02 % range typical, ±0.15 % reading + 0.05 % range maximum |
| Resolution: | .001/.01 |
| Measurements: | AC RMS |
| Ranges: | 30, 60A |
| DC Voltage Amplitude | |
| Accuracy: | 0.1% range typical, 0.25% range maximum |
| Resolution: | .01 |
| Measurements: | RMS |
| Ranges: | 30, 150, 300V |
| DC Current Amplitude | |
| Accuracy: | ±0.05 % reading + 0.02 % range typical, ±0.15 % reading + 0.05 % range maximum |
| Resolution: | .001/.01 |
| Measurements: | RMS |
| Ranges: | 30A |
| Convertible Source in AC Current Mode | |
| Accuracy: | ±0.05 % reading + 0.02 % range typical, ±0.15 % reading + 0.05 % range or ±12.5 mA whichever is greater |
| Resolution: | .001 |
| Measurements: | AC RMS |
| Ranges: | 5, 15A |
| Total Harmonic Distortion | Less than 0.1% typical, 2% maximum at 50/60 Hz |